E6581611G-47FCCS2Forward runReverse runHDRForward run (F) : Pressing forward run (F) rotates forward atthe specified frequency command value.Reverse run (R) : Pressing reverse run (R) rotates in reverseat the specified frequency command value.HD (S2): Pressing HD (S2) decelerates and stops.RFHDPowerSupplyNote 2)ONOFFONOFFONOFFONOFFForwardReverse0Note 3)OutputfrequencyNote 1) Set = (ST: standby) and = (terminal block) for 3 wire operation. Assign HD(operation hold) to any input terminal at input terminal selection. When assigning the S2 terminalas shown above, set = (HD: Operation hold).Note 2) If the terminals are ON before turning on the power, terminal input is ignored when the power isturned ON. (Prevents sudden movements.) After turning the power ON, turn terminal input ONagain.Note 3) When HD is OFF, F and R are ignored even when ON. R does not operate even if it's ON whenHD is ON. Likewise in this state, F does not operate even if it's ON. Turn F and R OFF and thenturn them ON.Note 4) During 3 wire operation, sending the jog run mode command stops operation.Note 5) Be aware that DC braking continues even if a startup signal is input during DC braking.Note 6) Only F and R maintain HD (operation hold). When using F or R in combination with otherfunctions, be aware that the other functions do not hold. For example, when F and SS1 areassigned, F holds, but SS1 does not.[Parameter settings]Terminal symbol Title Function Adjustment range Setting exampleS2 Input terminal selection 5 (S2) 0-203 50: HD (Operation hold)