E6581611F-13966.38.2 Using RS485■ Communication function settingsCommands and frequency settings are given priority by communication. (Prioritized by commands from thepanel or terminal block.) Thus, command and frequency settings from communication are activated,regardless of the command mode selection (cmod) or frequency settings mode selection settings (fmod).However, setting 48: SCLC (switching from communication to local) with input terminal function selection andwhen inputting from an external device, it is possible to operate at command mode selection (cmod) andfrequency setting mode selection (fmod) settings.Moreover, selecting local mode with the EASY key as Local / remote key function changes to panelfrequency/panel operation mode.■ Transmission specificationsItem SpecificationsCommunication protocol TOSHIBA inverter protocol MODBUS-RTUprotocolInterface RS485 compliantTransmission scheme Half duplex [Serial bus type (Line terminations resistor necessary atboth ends of system)]Wiring 2-wireTransmission distance 500 m max. (total length)Connection terminals 32max. (including upper host computer) Inverters connected in thesystem: 32max.Synchronization scheme Start-stop synchronizationCommunication baud rate 9600 bps to 38.4kbpsCharacter transmission JIS X0201 8-bit(ASCII) Binary codes fixed to 8 bitsBinary codes fixed to8 bitsError detecting scheme 1 Parity: Even/Odd/Non parity (selectable using a parameter)Error detecting scheme 2 Checksum CRCStop bit length Received by inverter : 1bit / Sent by inverter : 2 bitsOrder of bit transmission format Low-order bits transmitted firstCharacter transmission format 11-bit characters (Stop bit =1 , with parity)Inverter Number 0-99 0-63 (3Fh) 1-247Broadcast communicationInverter Number should be set to ** (*? or ?* (?=0-9) is available) 255 (0FFh)Inverter Numbershould be set to 0Frame length VariableError correction NoneResponse monitoring NoneOtherInverter operation at communication time-over: Select fromtrip/alarm/none¤ When alarm is selected, an alarm is output from the output terminal.When trip is selected, err5 blinks on the panel. PreviousNext |