Outputs [32] Galaxy Flex Installer Manual48Note: PA, PA Silent, PA Delay, PA Silent Delay and Fire are not included in the test when is used to include all zones. The response time of the zone circuits is reduced to20 ms (40 ms for RF RIOs) for the duration of the walk test to detect looseconnections or damaged wiring.Once the walk test has started, opening a zone (or a zone that is open at the start of the test)activates outputs programmed as entry/exit horn. If a single zone is open, the keypaddisplays the address and function of the zone. If multiple zones are open, the keypaddisplays how many zones are open. Use A or B to view the open zones.Note: The Walk Test option does not display the status of the zones. If an open zone isincluded in the walk test, the entry/exit horn activates as soon as the test is startedand remains active until the zone is closed.While the walk test is active the message WALK TEST ACTIVE / ESC to abort isdisplayed.Press # to view all zones that have been walk tested so far.To return to the walk test, press # again.Note: RF zones also record the signal strength in reduced gain mode.End the walk testTo end the walk test, press esc.The test ends automatically if no zones are activated for 20 minutes.To view the results of the test, access the event log (refer to Display Log [22]). The start ofthe walk test is indicated by the WALK TEST + message. Each tested zone is recorded (theactivation of each zone is recorded only once during the test, even if it was opened severaltimes). The end of the test is indicated by WALK TEST –.Outputs [32]Outputs are tested by function: for example, when you select 01=BELLS, all outputsprogrammed as Bells are activated. Refer to Program Outputs [53] for a full description ofeach output function.When you enter the Outputs option, output function type 01=BELLS is offered forselection.Press A or B to move to the required output function type, or enter the function type numberdirectly. For example enter 13 to select SECURITY.To test the selected output function press ent. Press ent to toggle the function ON and OFFas required.UsersUser types 5 and 6 have access to 01=BELLS and 02=STROBE only in the Output option.Only the engineer has access to all the output types.