Appendix G: Peripherals Galaxy Flex Installer Manual226Setup menuThe TouchCenter has a number of configuration settings that are set up directly within thekeypad. To access these settings, the TouchCenter must be in communication with the paneland the panel must be in Engineer mode. Proceed as follows:1. From the home screen, press the SECURITY button, and then enter the Authorizationcode. This is the Engineer PIN of the control panel. The Security screen is displayed.2. Press the MORE CHOICES button.3. Press the SETUP button.4. Press the TEST button.From this screen, the following options are available:Self DiagnosticsThese three diagnostic tests are provided to verify correct operation of the TouchCenter andto check the connection to the control panel: LCD Display Test Audio Test LED TestAddressIf required, use the option SERVICE to change the RS485 address. If changed, reconfigurethe TouchCenter with the control panel.TouchCenter operationFor general operation:1. On the homepage, press the required function button.Note: To program the control panel from the TouchCenter, press the Keypad Interfacebutton. The TouchCenter emulates a standard installer keypad.2. Enter a valid PIN when requested.3. Select the appropriate on-screen options. For help refer to the on-screen informationand to the separate user’s guide.You can set and unset the system by presenting a prox tag to the Proximity reader (see theinstructions in the help file on the home page).