E6582175E-105 Setting of electronic thermal protection characteristics selectionSetting value Overload protection Overload stall0 valid invalid1 valid valid2 invalid invalid3 invalid valid Setting of motor electronic thermal protection level 1 thr (Same as f173)When the capacity of the motor in use is smaller than the capacity of the inverter, or the rated current ofthe motor is smaller than the rated current of the inverter, adjust thermal protection level 1 thr for themotor in accordance with the motor's rated current.* When displaying as a percentage, 100% = rated output current (A) of the inverter is displayed.×0.6×1.0Output frequency (Hz)Output current reduction factor[%]/[A]030HzNote: The motor overload protection start level is fixed at 30Hz.[Example of setting: When the VFS15-2007PM-W1 is running with a 0.4kW motor having 2A ratedcurrent]Operationpanel action LED display OperationDisplays the output frequency. (Perform during operation stopped.)(When standard monitor display selection is set to 0[output frequency]) The first basic parameter “” (history function) is displayed. Turn the setting dial to change the parameter to . Parameter values can be read by pressing the center of the settingdial (default setting is 100%). Turn the setting dial to change the parameter to % (= motorrated current/inverter rated output current ×100=2.0/4.8×100)⇔ Press the center of the setting dial to save the changed parameter. and the parameter are displayed alternately.Note: The rated output current of the inverter should be calculated from the rated output current forfrequencies below 4kHz, regardless of the setting of the PWM carrier frequency parameter().MODE