E6582175F-10661) Emergency stop from terminalEmergency stop occurs at contact a or b. Follow the procedure below to assign a function to an inputterminal and select a stop method.[Parameter setting]Title Function Adjustment range Default settingf515 Deceleration time at emergency stop 0.0-3600 (360.0) (s) 10.0f603 Emergency stop selection0: Coast stop1: Deceleration stop2: Emergency DC braking3: Deceleration stop (f515)4: Quick deceleration stop5: Dynamic quick deceleration stop0f604 DC braking time during emergencystop 0.0-20.0 (s) 1.0f251 DC braking current 0 - 100 (%) 50Setting example) When assigning the emergency stop function to S2 terminalTitle Function Adjustment range Settingf114 Input terminal selection 4A (S1) 0 - 203 20: EXT (Emergencystop by external signal)Setting value 21 is reverse signal.Note 1) Emergency stopping via the specified terminal is possible, even during panel operation.2) Emergency stop from the operation panelEmergency stop from the operation panel is possible by pressing the STOP key on the panel twicewhile the inverter is not in the panel control mode.(1) Press the STOP key ............................. "eoff" will blink.(2) Press the STOP key once again .......... Operation will come to a trip stop in accordance with the settingof the f603 parameter.After this, "e" will be displayed and a failure detection signalgenerated (FL relay is activated).Note: While an emergency stop signal is input at a terminal, the trip cannot be reset. Clear the signal andthen reset the trip.