E6582175F-356 Setting of switching terminalsTo switch to motor 2, assign the following functions to a terminal not being used. It is also possible to switchto acceleration/deceleration 2 (AD2). Refer to section 6.27 for details.It is possible to set 3 functions for terminal F and R, and 2 functions for terminal S1 and RES.Input terminal function number Parameters changed from applicable parameters anddefault standards24AD226AD328VF232OCS2152MOT2OFF OFF OFF OFF OFF Default setting : pt, vl, vlv, vb, thr,acc, dec, fs02, f601ON OFF OFF OFF OFF acc→fs00, dec→f501, f502→fs03OFF ON OFF OFF OFF acc→fs10, dec→f511, f502→fs12OFF OFF ON OFF OFFDuring stop : pt→V/F constant, vl→f170,vlv→f171, vb→f172, thr→f173During run : vl→f170, vlv→f171,vb→f172OFF OFF OFF ON OFF f601 → f185- OFF - - ON→, →, → , →,→( is fixed when =or),→,→, →,→Note 1: Each of the following numbers (25, 27, 29, 33, 153) are reverse signals.Note 2: pt and "V/F constant" cannot be switched while running. Stop the motor before switching.When the motor is switched, wait for starting to drive for 0.2 seconds or more.vl and f170, vlv and f171, vb and f172 can be switched while running.Note 3: If motor is switched, the setting to retain and subtract an integral value of motor electronic thermal is possible.Refer to section 5.6 for details. Example of setting a terminal for switching: Sink logicF (F: Forward run)CCS2(VF2)S3(OCS2)S1(AD2)Forward run command2nd acceleration/deceleration switch2nd stall prevention operation switch2nd V/F setting switch