E6582175F-13366.34.6 Change display of the status monitorf711 to f718 : Status monitor 1 to 8Change monitor display items in the status monitor mode. Refer to chapter 8 for details.6.34.7 Change the status monitor conditionf709 : Standard monitor hold functionf746 : Status monitor filter FunctionThe standard monitor display can be hold.Some status monitors can be filtered to display.● If is set to , the monitored values selected with (standard monitor display selectionparameter) are displayed. For peak hold values and minimum hold values, the minimum values in eachoperation cycle are displayed. When the motor is at a standstill, the values monitored last are held as theywere until the motor is started the next time.The maximum and minimum values monitored after power is turned on is always displayed no matterwhether the motor is in operation or at a standstill.The maximum and minimum values are cleared to press the EASY key by setting f750 to 3.● “Output current”, “Input voltage”, “Output voltage” and “Torque” can be filtered by f746. Refer to chapter 8 about status monitor.[Parameter setting]Title Function Adjustment range Default setting Standard monitor hold function0: Real time1: Peak hold2: Minimum hold0f746 Status monitor filter 8-1000 (ms) 200f750 EASY key function selection0: Easy / standard setting mode switchingfunction1: Shortcut key2: Local / remote key3: Monitor peak / minimum hold trigger4: -5: -0