E6582175E-1655.7 Preset-speed operation (speeds in 15 steps)sr0 to sr7 : Preset-speed frequency 0 to 7f287 to f294 : Preset-speed frequency 8 to15f724 : Operation frequency setting target by setting dialFunctionA maximum of 15 speed steps can be selected just by switching an external logic signal. Multi-speedfrequencies can be programmed anywhere from the lower limit frequency to the upper limit frequency.[Setting method]1) Run/stopThe starting and stopping control is done from the terminal block.Title Function Adjustment range Setting Command mode selection0: Terminal block1: Panel keypad (including extension panel)2: RS485 communication3: CANopen communication4: Communication option02) Preset-speed frequency settinga) Set the speed (frequency) of the number of steps necessary.[Parameter setting]Preset-speed 0Title Function Adjustment range Default settingsr0 Preset-speed frequency 0 - (Hz) 0.0fmod Frequency setting mode selection 1 0-1314: sr0 0Frequency command set with sr0 is valid when fmod=14 (sr0).(sr0 is valid even when the command mode selection is not cmod=0.)Setting from speed 1 to speed 15Title Function Adjustment range Default setting- Preset-speed frequency 1-7 - (Hz) 0.0-