E6582175K-1111 Operation mode parametersTitle CommunicationNo. Function UnitMinimumsetting unitPanel/CommunicationAdjustment range DefaultsettingUsersetting Reference 0300 PWM carrierfrequencykHz 0.1/0.1 2.0 -16.0 12.0 6.18 0301 Auto-restartcontrol selection- - 0: Disabled1: At auto-restart after momentarystop2: At ST terminal off and on3: 1+24: At start-up0 5.9 0302 Regenerativepower ride-through control(Decelerationstop)- - 0: Disabled1: Regenerative power ride-throughcontrol2: Deceleration stop during powerfailure3: Synchronized acceleration /deceleration (signal)4: Synchronized acceleration /deceleration (signal + power failure)0 6.19.2 0303 Retry selection(number of times)Times 1/1 0: Disabled1-100 6.19.3 0304 Dynamic brakingselection- - 0: Disabled1: Enabled, Resistor overloadprotection enabled2: Enabled3: Enabled, Resistor overloadprotection enabled(At ST terminal on)4: Enabled (At ST terminal on)0 6.19.4 0305 Overvoltage limitoperation(Deceleration stopmode selection)- - 0: Enabled1: Disabled2: Enabled (Quick decelerationcontrol)3: Enabled (Dynamic quickdeceleration control)2 6.19.5 0306 Factory specificcoefficient 3L- - - - * 3 0307 Supply voltagecorrection(output voltagelimitation)- - 0: Supply voltage uncorrected,output voltage limited*1 6.19.61: Supply voltage corrected,output voltage limited2: Supply voltage uncorrected,output voltage unlimited3: Supply voltage corrected,output voltage unlimited 0308 Dynamic brakingresistanceΩ 0.1/0.1 1.0-1000 *2 6.19.4 0309 Dynamic brakingresistor capacitykW 0.01/0.01 0.01-30.00 *2 0310 Factory specificcoefficient 3A- - - - * 3 0311 Reverse-runprohibition- - 0: Forward/reverse run permitted1: Reverse run prohibited2: Forward run prohibited0 6.19.7 0312 Random mode - - 0: Disabled1: Random mode 12: Random mode 23: Random mode 30 6.18 0314 Factory specificcoefficient 3B- - - - * 3*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.*2: Default setting values vary depending on the capacity. Refer to section 11.4.*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.