E6582175J-210VoltageclassApplicablemotor(kW)Wire size (mm 2) Note 4)Braking resistor(optional) Grounding cableIECCompliantFor Japan*1IECCompliantFor Japan*13 phase240Vclass0.4 1.5 2.0 2.5 2.00.75 1.5 2.0 2.5 2.01.5 1.5 2.0 2.5 2.02.2 1.5 2.0 2.5 2.04.0 2.5 2.0 4.0 3.55.5 4.0 2.0 10 5.57.5 6.0 3.5 16 5.511 16 5.5 16 8.015 25 14 16 8.018.5 25 14 25 8.01 phase240Vclass0.2 1.5 2.0 2.5 2.00.4 1.5 2.0 2.5 2.00.75 1.5 2.0 2.5 2.01.5 1.5 2.0 2.5 2.02.2 1.5 2.0 4.0 3.53.0 1.5 2.0 4.0 3.53 phase500VClass0.4 1.5 2.0 2.5 2.00.75 1.5 2.0 2.5 2.01.5 1.5 2.0 2.5 2.02.2 1.5 2.0 2.5 2.04.0 1.5 2.0 2.5 2.05.5 1.5 2.0 4.0 3.57.5 2.5 2.0 6.0 3.511 4.0 2.0 10 5.515 6.0 3.5 16 5.518.5 10 5.5 16 5.5*1: For Japan: JEAC8001-2005 compliantNote 1: Sizes of the wires connected to the input terminals R/L1, S/L2 and T/L3 (Single-phase models are R/L1and S/L2/N) and the output terminals U/T1, V/T2 and W/T3 when the length of each wire does not exceed30m. If there is a need to bring the inverter into UL compliance, use wires specified in chapter 9.Note 2: For the control circuit, use shielded wires 0.75 mm 2 or more in diameter.Note 3: For grounding, use wires with a size equal to or larger than the above.Note 4: The wire sizes specified in the above table apply to HIV wires (copper wires shielded with an insulatorwith a maximum allowable temperature of 75°C) used at an ambient temperature of 50°C or less.Note 5: In case of aul=2 setting, contact your Toshiba distributor for wire size.