E6582175Q-217EnvironmentsLocation of use Indoors; not exposed to direct sunlight, corrosive gas, explosive gas, flammable gas,oil mist, or dust; and vibration of less than 5.9m/s2 (10 to 55Hz).Elevation 1000 m or lessAmbient temperature-10 to +40°C (50°C)Maximum Surrounding Air Temperature40 °C (with the protective label on the top of the inverter)50 °C (without the protective label on the top of t he inverter,except 0.75 kW or less in 200/240 V class)Storage temperature -25 to +70°C (Temperature appli cable for a short term.)Relative humidity 5 to 95% (free from condensation and vapor).Current reductionAccording to the carrier frequency f300 setting, you may need to reduce the inverter’s continuous output current.Reduction rates vary depending on the capacity of the inverter.[Single-phase/Three-phase 200/240V class]VFS15-VFS15S- Ambient temperatureInput voltage 200V to 240VPWM carrier frequency2.0k to 4.0kHz 4.1k to 12.0kHz2002PL-W1 40°C or less 1.5 A2004PM-W12004PL-W1 40°C or less 3.3 A2007PM-W12007PL-W1 40°C or less 4.8 A2015PM-W12015PL-W140°C or less 8.0 A 7.9 AAbove 40 to 50°C 8.0 A2022PM-W12022PL-W140°C or less 11.0 A 10.0 AAbove 40 to 50°C 11.0 A[Three-phase 200/240V class]VFS15- Ambient temperatureInput voltage 200V to 240VPWM carrier frequency2.0k to 4.0kHz 4.1k to 12.0kHz2037PM-W1 40°C or less 17.5 A 16.4 AAbove 40 to 50°C 17.5 A2055PM-W1 40°C or less 27.5 A 25.0 AAbove 40 to 50°C 27.5 A2075PM-W1 40°C or less 33.0 A 33.0 AAbove 40 to 50°C 33.0 A2110PM-W1 40°C or less 54.0 A 49.0 AAbove 40 to 50°C 54.0 A2150PM-W1 40°C or less 66.0 A 60.0 AAbove 40 to 50°C 66.0 ANote ) For 0.75 kW or less in 200/240 V class, maintain the ambient temperature of 40°C or less and th e PWM carrierfrequency of 4kHz or less for the compliance with UL standard. For "Above 40°C to 50°C" of the ambienttemperature except 0.75 kW or less in 200/240 V class, remove the protective label on the top of the inverter forthe compliance with UL standard.