E6582175A-321The space shown in the diagram is the minimum allowable space. Because air cooled equipment has coolingfans built in on the top or bottom surfaces, make the space on top and bottom as large as possible to allowfor air passage.Note: Do not install in any location where there is high humidity or high temperatures and where there arelarge amounts of dust, metallic fragments and oil mist. Calorific values of the inverter and the required ventilationAbout 5% of the rated power of the inverter will be lost as a result of conversion from AC to DC or from DC toAC. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, theinterior of the cabinet must be ventilated and cooled.The amount of forcible air-cooling ventilation required and the necessary heat discharge surface quantitywhen operating in a sealed cabinet according to motor capacity are as follows.Voltage class Inverter typeCalorific values (W)Note 1)Amount of forcible aircooling ventilationrequired (m 3/min)Heat dischargesurface area requiredfor sealed storagecabinet (m 3)Standbypowerrequirement(W)Note 2)4kHz 12kHz 4kHz 12kHz 4kHz 12kHzThree-phase240V class VFS15-2004PM-W12007PM-W12015PM-W12022PM-W12037PM-W12055PM-W12075PM-W12110PM-W12150PM-W135 40 0.20 0.23 0.70 0.80 1445.6 50 0.26 0.28 0.91 0.99 1481 92 0.46 0.52 1.61 1.85 1694.9 104 0.54 0.59 1.90 2.07 16139 154 0.79 0.87 2.77 3.08 18256 283 1.45 1.61 5.12 5.66 22305 367 1.73 2.08 6.10 7.34 22475 538 2.70 3.05 9.50 10.76 31557 628 3.16 3.56 11.14 12.56 31Single-phase240V class VFS15S-2002PL-W12004PL-W12007PL-W12015PL-W12022PL-W12337467910124.842.250901100.130.210.260.450.580.140.240.280.510.620.460.740.921.572.030.500.841.001.802.201414141616Three-phase500V class VFS15-4004PL-W14007PL-W14015PL-W14022PL-W14037PL-W14055PL-W14075PL-W14110PL-W14150PL-W130 39 0.17 0.22 0.61 0.78 1839 50 0.22 0.28 0.78 1.00 1858 76 0.33 0.43 1.15 1.53 1877 102 0.44 0.58 1.53 2.04 18131 156 0.75 0.88 2.63 3.12 20211 263 1.20 1.49 4.22 5.26 22254 346 1.44 1.96 5.08 6.92 22387 470 2.20 2.67 7.74 9.40 31466 572 2.65 3.25 9.32 11.44 31Note 1) Case of 100% Load Continuation operation. The heat loss for the optional external devices (input ACreactor, radio noise reduction filters, etc.) is not included in the calorific values in the tableNote 2) It is power consumption when power is on but is not output (0Hz), and cooling fan is activated (modelwith cooling fan).