E6582175G-277.2 Applied operations by an I/O signal (operation fromthe terminal block)Input terminal sink and source logic are set by using slide switch SW1.7.2.1 Input terminal function(sink logic)This function is used to send a signal to theinput terminal from an external programmablecontroller to operate or configure the inverter.The ability to select from a variety of functionsallows for flexible system design.Default settings of slide switch SW1and SW2 areas follows;SW1: PLC side, SW2: VIB side and S3 side.Refer to page B-11 to 13 for details. Settings for the logic input terminal functionTerminalsymbol Title Function Adjustment range Default settingF Input terminal selection 1A (F)0-203 Note 1)2 (F) Input terminal selection 1B (F) 0 (No function) Input terminal selection 1C (F) 0 (No function)R Input terminal selection 2A (R)0-203 Note 1)4 (R) Input terminal selection 2B (R) 0 (No function) Input terminal selection 2C (R) 0 (No function)RES Input terminal selection 3A (RES) 0-203 Note 1) 8 (RES) Input terminal selection 3B (RES) 0 (No function)S1 Input terminal selection 4A (S1) 0-203 Note 1) 10 (SS1) Input terminal selection 4B (S1) 0 (No function)S2 Input terminal selection 5 (S2) 0-203 Note 3) 12 (SS2)f146 Logic input / pulse train inputselection (S2)0: Logic input1: Pulse train input 0S3 Input terminal selection 6 (S3) 0-203 Note 4) 14 (SS3)f147 Logic input / PTC input selection (S3) 0: Logic input1: PTC input 0VIB Input terminal selection 7 (VIB) 0-203 Note 5) 16 (SS4)VIA Input terminal selection 8 (VIA) 8-55 Note 6) 24 (AD2)VIAVIB Analog/logic input selection (VIA/VIB) 0-4 0F to VIB Input terminal response time 1-1000 (ms) Note 7) 1VIC FMS3 FLA RYFLCFLBVIA CCVIBPP RCFCC RNO P24OUT STOCC +SUS2RES S1SINK SOURCESW1PLCVIBSW2PTC S3S4[Control terminal block]