E6582175K-4411 Table of output terminal functions 3FunctionNo. Code Function Action Reference92 DATA1 Designated data output 1 ON: bit0 of FA50 is ONOFF: bit0 of FA50 is OFF6.3893 DATA1N Inversion of designated data output 1 Inversion of DATA194 DATA2 Designated data output 2 ON: bit1 of FA50 is ONOFF: bit1 of FA50 is OFF95 DATA2N Inversion of designated data output 2 Inversion of DATA2106 LLD Light load output ON: Less than heavy load torque (f335~f338)OFF: heavy load torque (f335~f338) or more6.21107 LLDN Inversion of light load output Inversion of LLD108 HLD Heavy load output ON: Heavy load torque (f335~f338) or moreOFF: Less than heavy load torque (f335~f338)109 HLDN Inversion of heavy load output Inversion of HLD120 LLS Lower limit frequency stop ON: Lower limit frequency continuous operationOFF: Other than those above6.13121 LLSN Inversion of lower limit frequency stop Inversion of LLS122 KEB Power failure synchronized operation ON: Power failure synchronized operationOFF: Other than those above6.19.2123 KEBN Inversion of power failure synchronizedoperationInversion of KEB124 TVS Traverse in progress ON: Traverse in progressOFF: Other than those above6.40125 TVSN Inversion of traverse in progress Inversion of TVS126 TVSD Traverse deceleration in progress ON: Traverse deceleration in progressOFF: Other than those above127 TVSDN Inversion of traverse deceleration inprogressInversion of TVSD128 LTA Parts replacement alarm ON: Any one of cooling fan, control board capacitor, or maincircuit capacitor reaches parts replacement timeOFF: Any one of cooling fan, control board capacitor, or maincircuit capacitor does not reach parts replacement time6.29.15129 LTAN Inversion of parts replacement alarm Inversion of LTA130 POT Over-torque detection pre-alarm ON: Torque current is 70% of f616 setting value or moreOFF: Torque current is less than f616x70%-f6196.29.10131 POTN Inversion of over-torque detection pre-alarm Inversion of POT132 FMOD Frequency setting mode selection 1/2 ON: Select frequency setting mode selection 2 (f207)OFF: Select frequency setting mode selection 1 (fmod)5.8133 FMODN Inversion of frequency setting modeselection 1/2Inversion of FMOD136 FLC Panel / remote selection ON: Operation command or panelOFF: Other than those above6.2.1137 FLCN Inversion of panel / remote selection Inversion of FLC138 FORCE Forced continuous operation in progress ON: Forced continuous operation in progressOFF: Other than those above6.30139 FORCEN Inversion of forced continuous operation inprogressInversion of FORCE140 FIRE Specified frequency operation in progress ON: Specified Frequency operation in progressOFF: Other than those above141 FIREN Inversion of specified frequency operation inprogressInversion of FIRE