E6582175E-455.2 Setting acceleration/deceleration time : Acceleration time 1 : Setting of acceleration/deceleration time unit : Deceleration time 1 : Automatic acceleration/deceleration Function1) For acceleration time 1 programs the time that it takes for the inverter output frequency to gofrom 0.0Hz to maximum frequency .2) For deceleration time 1 programs the time that it takes for the inverter output frequency to gofrom maximum frequency to 0.0Hz.Output frequency (Hz)Time [sec]O (Manual setting)[Parameter setting]Title Function Adjustment range Default setting Acceleration time 1 0.0-3600 (360.0) (s) 10.0 Deceleration time 1 0.0-3600 (360.0) (s) 10.0 Setting of acceleration/decelerationtime unit0: -1: 0.01s unit (after execution: 0)2: 0.1s unit (after execution: 0)0Note1): Setting increment unit can be changed to 0.01 seconds by parameter f519.Note2): f519=2: When the acceleration/deceleration time is set to 0.0 seconds, the inverter acceleratesand decelerates 0.05 seconds.f519=1: When the acceleration/deceleration time is set to 0.00 seconds, the inverter acceleratesand decelerates 0.01 seconds.● If the programmed value is shorter than the optimum acceleration/deceleration time determined by loadconditions, overcurrent stall or overvoltage stall function may make the acceleration/deceleration timelonger than the programmed time. If an even shorter acceleration/deceleration time is programmed, theremay be an overcurrent trip or overvoltage trip for inverter protection. (Refer to section 13.1 for details)