E6582175Q-5 17(1) Input withstand rating is that for which the product has been designed thermally.(2) Output interrupt rating relies on Integral solid state short circuit protection. This does not provide branch circuitprotection. Branch circuit protection must be provided in accordance with the National Electrical Code and anyadditional local codes. This is dependant on the type of installation.In case of using with a higher AIC capability up to 100kA(*1), the Short Circuit Current Ratings (SCCR) become 100kA(*1)by installing with the circuit breakers(GV3P) or the fuses listed in Table 4.Table 4 AIC 100kA, Fuses, Circuit breakers and Wire sizesInverter model Voltage(V)Branch circuit protectionCable sizes ofpower circuit Earth CableWith Fuses With circuit breakersClass (*2) Rating(A)Type-Form(*3)Setting(A)VFS15-2004PM-W1 240 Class J 10 GV3P13 9 AWG 14 AWG 14VFS15-2007PM-W1 240 Class J 15 GV3P13 9 AWG 14 AWG 14VFS15-2015PM-W1 240 Class J 25 GV3P13 10 AWG 14 AWG 14VFS15-2022PM-W1 240 Class J 25 GV3P18 18 AWG 12 AWG 14VFS15-2037PM-W1 240 Class J 45 GV3P25 25 AWG 10 AWG 10VFS15-2055PM-W1 240 Class J 60 GV3P40 40 AWG 8 AWG 10VFS15-2075PM-W1 240 Class J 70 GV3P50 50 AWG 6 AWG 10VFS15-2110PM-W1 240 Class J 100 GV3P65 65 AWG 6*2 AWG 8VFS15-2150PM-W1 240 Class J 110 AWG 6*2 AWG 8VFS15S-2002PL-W1 240 Class J 10 GV3P13 9 AWG 14 AWG 14VFS15S-2004PL-W1 240 Class J 15 GV3P13 9 AWG 14 AWG 14VFS15S-2007PL-W1 240 Class J 25 GV3P13 13 AWG 14 AWG 14VFS15S-2015PL-W1 240 Class J 40 GV3P25 25 AWG 10 AWG 12VFS15S-2022PL-W1 240 Class J 45 GV3P32 32 AWG 10 AWG 10VFS15-4004PL-W1 480 Class J 6 GV3P13 9 AWG 14 AWG 14VFS15-4007PL-W1 480 Class J 6 GV3P13 9 AWG 14 AWG 14VFS15-4015PL-W1 480 Class J 15 GV3P13 9 AWG 14 AWG 14VFS15-4022PL-W1 480 Class J 15 GV3P13 10 AWG 14 AWG 14VFS15-4037PL-W1 480 Class J 25 GV3P13 13 AWG 12 AWG 14VFS15-4055PL-W1 480 Class J 40 GV3P18 18 AWG 10 AWG 10VFS15-4075PL-W1 480 Class J 40 GV3P25 25 AWG 8 AWG 10VFS15-4110PL-W1 480 Class J 60 GV3P32 32 AWG 8 AWG 10VFS15-4150PL-W1 480 Class J 70 GV3P40 (*1) 40 AWG 6 AWG 10(*1) In case VFS15-4150PL with the circuit breaker, the Short Circuit Current Ratings (SCCR) is 65kA.(*2) The manufacturer of the fuses should be "Cooper Bussmann" or "Mersen" (formerly, "Ferraz Shawmut") for thecompliance of UL standard.(*3) The manufacturer of the listed circuit breaker is "Schneider Electric".