E6582175J-310 Selection of wiring devicesVoltageclassApplicablemotor(kW)Input current (A) Molded case circuit breaker (MCCB)Earth leakage circuit breaker (ELCB)Magnetic contactor (MC)Note 2) Note 3)WithoutDCL With DCL Rated current (A) Rated current (A)Without DCL With DCL Without DCL With DCL3 phase240Vclass0.4 3.6 1.8 5 5 20 200.75 6.3 3.4 10 5 20 201.5 11.1 6.5 15 10 20 202.2 14.9 9.2 20 15 20 204.0 23.8 15.9 30 20 32 205.5 35.6 21.5 50 30 50 327.5 46.1 28.9 60 40 60 3211 63.1 41.5 100 60 80 5015 82.1 55.7 125 75 100 6018.5 89.1 70.0 125 100 100 801 phase240Vclass0.2 3.4 2.0 5 5 20 200.4 5.9 4.0 10 5 20 200.75 10.0 7.6 15 10 20 201.5 17.8 14.6 30 20 32 202.2 24.0 20.1 30 30 32 323.0 24.0 23.6 30 30 32 323 phase500VclassNote 6)0.4 2.1 0.9 5 5 20 200.75 3.6 1.8 5 5 20 201.5 6.4 3.4 10 5 20 202.2 8.8 4.8 15 10 20 204.0 13.7 8.3 20 15 20 205.5 20.7 11.2 30 15 32 207.5 26.6 15.1 40 20 32 2011 36.6 21.7 50 30 50 3215 47.7 29.0 60 40 60 3218.5 52.7 36.3 75 50 60 50The recommended molded case circuit breaker (MCCB) must be connected to primary side of each inverter toprotect the wiring system.Note 1: Selections for use the Toshiba 4-pole standard motor with power supply voltage of 200V/ 400 - 50Hz.Note 2: Be sure to attach a surge absorber to the exciting coil of the relay and the magnetic contactor.Note 3: When using the auxiliary contacts 2a of the magnetic contactor MC for the control circuit, connect thecontacts 2a in parallel to increase reliability.Note 4: When a motor is driven by commercial power supply using commercial power supply / inverter switchingcircuit, use a magnetic contactor appropriated AC-3 class the motor rated current.Note 5: Select an MCCB with a current breaking rating appropriate to the capacity of the power supply, becauseshort-circuit currents vary greatly depending on the capacity of the power supply and the condition of thewiring system. The MCCB, MC and ELCB in this table were selected, on the assumption that a powersupply with a normal capacity would be used.Note 6: For the operation and control circuits, regulate the voltage at 200V to 240V with a step-down transformerfor 500V class.Note 7: In case of aul=2 setting, be sure to select the wiring device for 1 rating up motor.Note 8: Regarding influence of leakage current, refer to section 1.4.3.