Chapter 9. DiagnosticsGFK-2950C February 2018 4139.4.13 Constant Sweep Time Exceeded (Group 19)The fault group Constant Sweep Exceeded occurs when the CPU operates in Constant Sweep modeand detects that the sweep has exceeded the constant sweep timer. In the fault extra data, theDWORD at byte offset 8 contains the amount of time that the sweep went beyond the constantsweep time (in microsecond units). Stored in Big Endian format.Action: Non-configurable.0, Constant SweepCorrectionIf Constant Sweep (0):1) Increase constant sweep time.2) Remove logic from application program.Note: Error code 1 is not used.9.4.14 System Fault Table Full (Group 20)The fault group System Fault Table Full occurs when the Controller Fault Table reaches its limit.Action: Non-configurable.0, System Fault Table FullCorrectionClear the Controller Fault Table.9.4.15 I/O Fault Table Full (Group 21)The fault group I/O Fault Table Full occurs when the I/O Fault Table reaches its maximum configuredlimit. To avoid loss of additional faults, clear the earliest entry from the table.Action: Non-configurable.0, I/O Fault Table FullCorrectionClear the I/O Fault Table.