E6581595E-1755.11 Selecting control mode : V/F control mode selection• FunctionWith VF-nC3, the V/F controls shown below can be selected.{ V/F constant{ Variable torque{ Automatic torque boost control *1{ Vector control *1{ Energy saving *1(*1) Parameter setting macro torque boost: parameter can automatically set this parameter and auto-tuning at a time.Q Parameter settingTitle Function Adjustment range Default setting V/F control mode selection0: V/F constant1: Variable torque2: Automatic torque boost control3: Vector control4: Energy-saving0Note: (V/F control mode selection) is valid only for the first motor.Changes to "V/F constant control" when switching to the second motor, regardless of the setting.Steps in setting are as follows(In this example, the V/F control mode selection parameter is set to (Vector control).[Setting V/F control mode selection to 3 (sensorless vector control)]Operation panelaction LED display Operation. Displays the operation frequency. (Perform during operation stopped.)(When standard monitor display selection is set to [Operation frequency]) The first basic parameter “” (history function) is displayed. Rotate the settings dial to the right, and change the parameter to (control selection). Parameter values can be read by pressing the center of the settingdial (the default setting is :V/F constant). Rotate the settings dial to the right, and change the parameter to (vector control).⇔ Press the center of the setting dial to save the changed parameter. and parameter set value “” are displayed alternately.MODEefesotomasyon.com -Toshiba inverter,drive,servo,plc