E6581595G-37 Connecting1) For contact input aCCInput terminal¹Operates by short circuiting between theinput terminal and CC (common). Use forforward rotation, reverse rotation, andmulti-stage speed.Inverter Contact switch a With sink settings2) For connection (sink logic) via transistor output¹Control by connecting the input terminal and CC(common) to the output (non-contact switch) of theprogrammable controller. Use for forward rotation,reverse rotation, and multi-stage speed. Use a 5 mAtransistor that operates at 24 V dc.CCInput terminalInverter Programmable controller∗ About programmable controllers and interfaces If controlling the inverter using an open collector outputprogrammable controller, the following error signals are sent to the inverter. This is a result of differences in theheight of control power supply potential when the inverter remains ON and the programmable controller is turnedOFF. Always set the inverter lock to prevent the programmable controller from being turned OFF while theinverter is ON.External+24 V power supplyP24COMFuseBlown fusedetection circuitInside the inverter+24 V power supply+24 VProgrammable controller Inverterefesotomasyon.com -Toshiba inverter,drive,servo,plc