E6581595K-711Title CommunicationNo. Function UnitMinimumsetting unitPanel/CommunicationAdjustment range DefaultsettingUsersetting Reference 0287 Preset-speedfrequency 8Hz 0.1/0.01 - 0.0 0288 Preset-speedfrequency 9Hz 0.1/0.01 - 0.0 0289 Preset-speedfrequency 10Hz 0.1/0.01 - 0.0 0290 Preset-speedfrequency 11Hz 0.1/0.01 - 0.0 0291 Preset-speedfrequency 12Hz 0.1/0.01 - 0.0 0292 Preset-speedfrequency 13Hz 0.1/0.01 - 0.0 0293 Preset-speedfrequency 14Hz 0.1/0.01 - 0.03.66.10 0294 Preset-speedfrequency 15Hz 0.1/0.01 - 0.0• Operation mode parametersTitle CommunicationNo. Function UnitMinimumsetting unitPanel/CommunicationAdjustment range DefaultsettingUsersetting Reference 0300 PWM carrierfrequencykHz 1/1 2 -16 12 6.11 0301 Auto-restartcontrol selection- - 0: Disabled1: At auto-restart after momentarystop2: At ST terminal off and on3: 1+24: At start-up0 6.12.1 0302 Regenerativepower ride-through control(Decelerationstop)- - 0: Disabled1: Automatic setting2: Slowdown stop0 6.12.2 0303 Retry selection(number of times)Times 1/1 0: Disabled1-100 6.12.3 0305 Overvoltage limitoperation(Slowdown stopmode selection)- - 0: Enabled1: Disabled2: Enabled (Quick decelerationcontrol)3: Enabled (Dynamic quickdeceleration control)2 6.12.4efesotomasyon.com -Toshiba inverter,drive,servo,plc