E6581595J-210 Selection of wiring devicesInput current(A)No-fuse breaker (MCCB)Earth leakage breaker (ELCB)Magnetic contactor(MC)Overload relay(THR)No reactor with DCL No reactor with DCLVoltageclassApplicablemotor(kW)r NoreactorWithDCL Ratedcurrent(A)MCCB type(ELCB type)Ratedcurrent(A)MCCB type(ELCB type)Ratedcurrent(A)ModelRatedcurrent(A)ModelAdjustmentcurrent (A)referencevalueModel0.1 3.5 - 5 - 13 - 0.70.2 6.0 - 10 - 13 - 1.30.4 11.4 - 15 - 13CA13- 2.3Single-phase100Vclass 0.75 18.9 - 30NJ30E(NJV30E)--19 CA20 --3.6TH13U0.1 2.0 1.2 5 5 13 13 0.70.2 3.4 2.1 5 5 13 13 1.30.4 5.9 4.1 10 5 13 13 2.30.75 10.2 7.7 15 10 13CA1313 3.61.5 17.8 14.8 20 15 19 CA20 13CA136.8Single-phase200Vclass2.2 24 20.3 30NJ30E(NJV30E)30NJ30E(NJV30E)26 CA25 19 CA20 9.3TH13U0.1 1.2 0.6 5 5 13 13 0.70.2 2 0.9 5 5 13 13 1.30.4 3.6 1.8 5 5 13 13 2.30.75 6.3 3.5 10 5 13 13 3.61.5 11.1 6.6 15 10 13 13 6.82.2 14.9 9.3 20 15 13CA1313CA139.3TH13UThree-phase200Vclass4.0 23.8 16.1 30NJ30E(NJV30E)30NJ30E(NJV30E)26 CA25 19 CA20 15 TH20UNote 1: Models made by Toshiba Industrial Products Sales Corporation are shown.Note 2: Be sure to attach a surge killer to the exciting coil of the relay and the magnetic contactor.Note 3: When using the auxiliary contacts 2a of the magnetic contactor MC for the control circuit, connect thecontacts 2a in parallel to increase reliability.Note 4: Select an MCCB with a current breaking rating appropriate to the capacity of the power supply, becauseshort-circuit currents vary greatly depending on the capacity of the power supply and the condition of thewiring system. The MCCB, MC, THR and ELCB in this table were selected, on the assumption that apower supply with a normal capacity would be used.efesotomasyon.com -Toshiba inverter,drive,servo,plc