E6581595F-646Q Settings for run/stop via communicationTitle Function AdjustmentrangeStandarddefaults Setting example Command mode selection ~ (panel) (RS485communications)Q Settings for speed command via communicationTitle Function AdjustmentrangeStandarddefaults Setting example Frequency setting modeselection ~ (Setting dial) (RS485communications)Q Communication function parameters (2-wire RS485 communication)Communication speed, parity, inverter number, and communication error trip time settings can be changedvia panel operations or communication.Title Function Adjustment range Default setting Baud rate3: 9600bps4: 19200bps5: 38400bps4 Parity0: NON (No parity)1: EVEN (Even parity)2: ODD (Odd parity)1 Inverter number 0-247 0 Communication time-out time 0: Desabled (*)1-100 (s) 0.0 Communication time-out action0: Alarm only1: Trip (coast stop)2: Trip (slowdown stop)0 Communication time-outdetection condition0: Always1: When or isselected for communication2: 1 + during operation1 Selection of communicationprotocol0: Toshiba inverter protocol1: ModbusRTU protocol 0 Block write data 1 0 Block write data 20: No selection1: Command information2: -3: Frequency setting value4: Output data on the terminalboard5: Analog output forcommunication0efesotomasyon.com -Toshiba inverter,drive,servo,plc