E6581595C-1333.4 Meter setting and adjustment : Meter selection : Meter adjustment gain• FunctionOutput of 0 - 1 mAdc, 0 (4) - 20 mAdc, 0 - 10 vdc can be selected for the output signal from the FMterminal, depending no the setting. Adjust the scale at .Use an ammeter with a full-scale 0 - 1 mAdc meter.The (analog output bias) needs to be adjusted if output is 4 - 20 mAdc.[Connected meter selection parameters]Title Function Adjustment range Supposition output atfsl=17 Default setting Meterselection0: Output frequency1: Output current2: Frequency reference3: Input voltage (DC detection)4: Output voltage (command value)5 - 11: -12: Frequency setting value (aftercampensation)13: VI input value14: -15: Fixed output 1 (output current 100%equivalent)16: Fixed output 2 (output current 50%equivalent)17: Fixed output 3 (other than theoutput current)18: RS485 communication data19:For adjustments ( set value isdisplayed.)20 - 22: -Maximum frequency ()-Maximum frequency (fh)1.5x rated voltage1.5x rated voltage-Maximum frequency (fh)Maximum input value----Maximum value (100.0%)--0Meteradjustmentgain- - -efesotomasyon.com -Toshiba inverter,drive,servo,plc