E6581595E-1355.6 Meter setting and adjustment : Meter selection : Meter adjustmentFor details, see 3.4.5.7 Forward/reverse run selection (Panel keypad) : Forward/reverse run selection (Panel keypad)• FunctionProgram the direction of rotation of the motor when the running and stopping are made using the RUNkey and STOP key on the operation panel.Valid when (command mode) is set to (operation panel). Parameter settingTitle Function Adjustment range Default setting Forward/reverse run selection(Panel keypad)0: Forward run1: Reverse run2: Forward run (F/R switching onremote keypad)3: Reverse run (F/R switching onremote keypad)0+ When is set to , the standard monitor is displayed, pressing the FWD/REV key on the extensionpanel (option RKP007Z) changes the direction of rotation from reverse to forward after displaying themessage .Pressing the FWD/REV key again changes the direction of rotation from reverse to forward afterdisplaying the message .+ Check the direction of rotation on the status monitor. For monitoring, see8.1: Forward run: Reverse run+ When the F and R terminals are used for switching between forward and reverse rotation from theterminal board, the forward/reverse run selection parameter is rendered invalid.Short across the F-CC terminals: forward rotationShort across the R-CC terminals: reverse rotation.+ The inverter was factory-configured by default so that shorting terminals F-CC and terminals R-CCsimultaneously would cause the motor to slow down to a stop.Using the parameter , however, you can select between forward run and reverse run.efesotomasyon.com -Toshiba inverter,drive,servo,plc