E6581595F-166<>Q If two signals are impressed simultaneously• If a clear single and an up or down signal are impressed simultaneously, priority will be given to theclear signal.• If up and down signals are impressed simultaneously, The frequency will change at the specified upor down rate.Q About the setting of the initial up/down frequencyTo adjust the frequency starting at a specified frequency other than 0.0 Hz (default initial frequency)after turning on the inverter, specify the desired frequency using (initial up/down frequency).Q About the change of the initial up/down frequencyTo make the inverter automatically save the frequency immediately before it is turned off and startoperation at that frequency next time power is turned on, set (change of initial up/downfrequency) to 1 (which changes the setting of when power is turned off).Keep in mind that the setting of is changed each time power is turned off.Q Frequency adjustment rangeThe frequency can be set from 0.0Hz to (Maximum frequency). The lower-limit frequency will beset as soon as the set frequency clearing function (function number 92, 93) is entered from the inputterminal.Q Minimum unit of frequency adjustmentIf (Frequency free unit magnification) is set to 1.00, the output frequency can be adjusted insteps of 0.01Hz.Forward / reversecommandUP signalDOWN signalSet frequencyclearing signalUpper limit frequencyCommand frequency(Hz)(The dotted lines representeffective output frequencies)OHzefesotomasyon.com -Toshiba inverter,drive,servo,plc