Checking device STATUSLoop Device StatusTo list the STATUS of a device on an allocated loop at the Control Panel: Press Menu On/Offbutton and then select [Info], momentarily press to select [Status] -> [Device], enter thedevice number, select [Loop], enter the loop number n on which the device resides, select [Enter]to view device status information.Analogue Channel 1 is forward scatter optical smoke sensorAnalogue Channel 2 is heat sensorAnalogue Channel 3 is for CO gas sensorAnalogue Channel 4 is for backward scatter optical smoke sensorAnalogue Channel 5 reports sounder/flasher/speech faults to the control panelAnalogue Channel 6 reports monitored input/monitored output faults to the control panelO - Output, I - Input and . signify - not usedDevice digital I / O channelsS4 Dual OH/Red VAD O . . O 1, 2, 4, 5S4 Heat/Voice Sen Sndr/Red VAD OOOO 2, 5S4 Dual OH/Voice Sen Sndr/Red VAD . OOO 1, 2, 4, 5S4 Dual OH/CO/Voice Sen Sndr/Red VAD OOOO 1, 2, 3, 4, 5S4 Dual OH/White VAD O . . O 1, 2, 4, 5S4 Dual OH/White VAD (HP) O . . O 1, 2, 4, 5S4 Dual OH/Voice Sndr/White VAD (Std) OOOO 1, 2, 4, 5S4 Dual OH/Voice Sen Sndr/White VAD (HP) OOOO 1, 2, 4, 5S4 Heat/Voice Sndr/White VAD (HP) OOOO 2, 5S4 Dual OH CO/Voice Sen Sndr / White VAD (HP) OOOO 1, 2, 3, 4, 5S4 Dual OH/Voice Sounder . OOO 1, 2, 4, 5S4 OH Sensor Sounder . OOO 1, 2, 5S4 Dual OH Sensor Sounder . OOO 1, 2, 4, 5S4 Heat Sensor Sounder . OOO 2, 5S4 Dual OH CO Sensor . . . O 1, 2, 3, 4, 5S4 Heat Sensor . . . O 2S4 Heat Sensor Sounder . OOO 2, 5S4 Dual Optical Heat Sensor . . . O 1, 2, 4S4 Dual Optical Heat Sensor CO . . . O 1, 2, 3, 4, 5S4 Dual Optical Heat Sensor Sounder . OOO 1, 2, 4, 5+ Monitored input 6+ Monitored output 6Other devicesBeam transmitter . . . O 2Beam receiver . . . O 1- raw data2- averagedata4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms. 65Vigilon 4/6 loops & Compact (VA) panels & network nodesChecking device STATUSLoop 1 No. 7 Dual optical/Heat/COLB1:C End1:Hi End2:HiI/O:...0 Anal:1-42nd:250 3rd:0 Short delay:0Zone 1 Zone 1LED),6Loop on whichthe device is installedLocation of thedevice on the loopDevice descriptionMonitored Input / LED isattached to the deviceLoop breakerconditionC:closedStatus of End 1of the device(high or low)Status of End 2of the device(high or low)DigitalInput outputsAnalogue channelsused1:Optical (forward)2:Heat3:Gas4:Optical (Backward)5:Sounder/VAD (Strobe)/Speech fault6:Monitored line or LEDSecondary addressdenotes group of devicesTertiary addressused primarily bysounders/VAD (strobe)Short circuit delayassociated withnumber of T breakersoff T breakersZone number and label