4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms. 149Vigilon 4/6 loops & Compact (VA) panels & network nodesAppendix C - Guidelines for standalone system commandsTime slots and Time blocksTime slotsA Time slot must be linked with a Time block. It is the Time block that perform actions on the system." Timeslots do not process when the panel is in a fire condition.¨ a Time slot can be:• triggered automatically• switched ON / OFF manually• or switched ON / OFF by Command build¨ it performs an action immediately or after a delay of 0 to 24 hours.¨ There can be up to 16 Time slots per panel¨ each Time slot has to be given an Enable time and aDisable time¨ each Time slot must be ANDed / ORed to the days ofweek, (Mon, Tue, Wed, Thu, Fri, Sat, Sun).¨ when a Time slot is ANDed with selected days, it willonly operate on the selected days¨ when a Time slot is ORed with selected days, it will beEnabled during selected times and will remain ONthroughout the days selected.Time blocksA Time block is used to perform periodic enable disable action onthe system.¨ There are 0 - 15 Time blocks per panel¨ the Time block 0 is always in the Enable state and is thedefault for all sensors¨ a Time block can be linked to one or more Time slots¨ when a Time slot is enabled the time block it is linked tois also Enabled¨ a sensor or interface input can only be assigned to oneTime block¨ when a Time block is in an Enable state:• any sensor(s) linked to it will operate in the Enablestate that has been set up• any Command build linked to it is triggered.¨ when a Time block is in a Disabled state any Zone taskslinked to it are also Disabled.COMMANDBUILDENABLE TIMEDISABLE TIME08:0017:00TIMESLOT 1ACTIONDAYS: MON TUE WEDTHU FRI SAT SUNAND(BOTH)OR(EITHER)DELAYED BY 0 - 24 hrsTIMEDAYS SETUPAND/ORTIMEBLOCK 1TIMESLOT 1TIMESLOT 2TIMESLOT 3TIMESLOT 4TIMESLOT 16SETUPENABLE STATEDISABLE STATE015DEVICE NO. = "X"SETUPENABLE STATEDISABLE STATE813DEVICE NO. = "X"SETUPTRIGGERMAXIMUM OF 16 PER PANEL MAXIMUM OF 15 PER PANELENABLE / DISABLE TIMESLOTCOMMAND BUILD NO. "Y"SETUP ZoneNOTE: A Timeblock may contain any multiple Timeslots.A Timeslot may be linked to any number of Timeblocks.The default is for all the devices to be in Time block 0.A Timeblock is enabled if any one of the Timeslots withinit is in the enable state.A COMMAND BUILD LINKEDTO A TIMEBLOCK WILL BETRIGGERED WHEN THETIMEBLOCK IS ENABLEDAND REVERSED WHEN THETIMEBLOCK IS DISABLED.