Useful menu optionsThe menu maps of all the menu options that are accessible at the control panel are detailed inAppendix A.Panel Buzzer¨ It may be necessary during commissioning to disable the panel buzzer. It is possibleto selectively switch the disablement, fault, fire and supervisory buzzer sound to Offor On. It is important to ensure that the buzzers are switched On for normal operationafter commissioning.# - will appear if a PIN is setup.Press Menu On/Off button and then select [Test/Eng] -> [UserCode]# and select [Config], [Buzzer] this will allow selection of [Disable], [Fault], [Fire] or[Supervis] and then select [On/Off] and [Enter]."There is no indication given at the panel of buzzer disablement.Software version checkThe software version of the panel can be displayed by viewing the status of the master controlboard / Main control card.To check the software version of the Master control board / Main control card: Press Menu On/Offbutton and then select [Info], momentarily press to select [Status] -> [Card] and enter Cardnumber 0, which is the Main control board / Master control card and then select [Enter]. Thedisplay will show software version number and date of release.Password or PIN code" The terms Password, PIN (Personal Identification Number), Usercode andAccess code mean the same and are used interchangeably.A password restricts access to the controls available to the user at the Control panel.There are three access levels to the controls. These are access level 1, 2 and 3.¨ The Access level 1 controls only allow cycling through of multiple fire eventsmessages on the screen using the two buttons on the outer door.¨ Access level 2a is for the CUSTOMER. Here the person responsible for the systemcan access the 'essential controls' by opening the panel outer door using a key¨ Access level 2b is for the CUSTOMER. Here the person responsible for the systemcan access essential controls and some configuration menus using the panel door keyplus a customer PIN.¨ Access level 3 is for the ENGINEER. Here the person responsible for the system canaccess essential controls and all system menus using the panel door key plus EngineerPIN.¨ Daily PINThere is another password that changes daily, which is available to the servicingorganisation. This daily password provides the same access to controls as theEngineers' PIN. The daily PIN is only used when the Engineer's PIN is not known." Always make a note of the Customer and Engineering PINs once they arecreated. Ensure the Customer PIN is passed on to the person responsible for the firealarm system on the site.4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms. 53Vigilon 4/6 loops & Compact (VA) panels & network nodesUseful menu options