4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms. 83Vigilon 4/6 loops & Compact (VA) panels & network nodesInstalled equipment testsS Cubed" The remote control is only operable when the panel is in the Zone Testmode for an EN system or Commission mode for a BS system.¨ Depending on thetype of S-Cubeddevice beingcommissioned checkto ensure correctoutput sound tone,speech message andVAD/strobe rate aregiven. The S-Cubeddevices should havebeen setup using thecommissioning tool.¨ The volume of thesounder S-Cubeddevice can beadjusted by using aremote control.¨ Each S-Cubed shouldbe tested for correctoperation in the eventof fire.¨ The sound levels inthe areas should betested in accordancewith the BritishStandardrequirements and tomeet the site specificneeds, as agreed withthe customer.Repeat panel (Loop connected)Each loop repeat panel should be tested for the following:¨ System event messages and indications are given¨ Local fault events, such as Battery and Mains supply disconnection¨ Alarm controls & Cancel Buzzer operation is possibleMimic PanelEach Mimic indicator panel should be configured and tested for the following:¨ To confirm fires are indicated¨ Local fault events, such as Battery and Mains supply disconnection¨ Lamp Test• On an A3 Mimic panel by pressing the button on the centre face of the unit• On an A2 mimic panel (Legacy panel) by operating the test key• On an A4 mimic panel (legacy panel) by inserting a 2mm pin like object (for example asmall terminal screwdriver) into a hole located on the underside of the panel enclosure.Mains powered DAU and micro DAU (Legacy devices)Each Mains powered DAU and micro DAU should be configured and tested for the following:¨ Check to ensure correct output sound tone and speech message are given of fire events.¨ Adjust the volume out at speakers on the Speaker circuits using controls on the Mainspowered DAU in accordance with the British Standard requirements and to meet the sitespecific needs as agreed with the customer.Similarly volume level should be adjusted at each micro DAU to the required setting duringcommissioning.VIGILON Compact VA system (Legacy system)¨ A 'Fall back' test must be performed to ensure the central messages are announced. This isachieved by stopping the two loops using the [Test/Eng] menu and then by conducting aSound Alarm from the panel. Restart the loop on completion of the test.Deviations from standards¨ The results of system tests carried out must be in accordance with the relevant standardsand project specification.¨ Any deviations must be documented and reported for approval.Thinnedsectionon base3m - maximum rangePress the function button to toggle between:function and note the Red LED flashes x2 every 2 secondsToneVolume function and note the Red LED flashes x1 every 2 secondsPress the button to increase or to select the nextPress the button to decrease or to select the previousvolume tonevolume tone+-Wall Sounder device+-Red LEDFlashSteady OnPerform a short press on the Power buttonto turn On the remote control. The Red LED willflash x1 every 2 secondsOffPress and hold the Power button to save the adjustments made.The Red LED will remain On whilst the button is held pressed.The data is saved to the device when the tone/speech on the S-Cubed unitstops briefly. Release the button on the remote control and theRed LED will switch Off to complete the adjustment process.Note: The VAD/strobe light on the S-Cubed unit if fitted will flash rapidly whenthe volume is being adjusted using the remote control.Remote ControlTrouble shootingIf the remote control fails to operate in closeproximity to the thinned section of the Sounderdevice, then a possible cause may bedischarged battery. In which case replace thebattery.