Commissioning instructions156 4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.Appendix C - Guidelines for standalone system commandsFire Protection Equipment (FPE)¨ There can more than one Interface configured FPE application in a Vigilon System.FPE Interface can be a MV Interface unit S4-34411, but can be also be a S4-34415 or S4-34420.Other interface units can also be configured as FPE, these include S4-34440-02, S4-34440-12, S4-34401 andS4-34404.¨ a FPE Interface device is automatically placed in plant Sector 32 (as default) and is unaffected by operation ofSOUND ALARMS control¨ a FPE Interface device may be Enabled or Disabled from the panel menus select:Menu On/Off button to select: [Control] -> [Enable] / [Disable] -> -> -> -[FPE] -> [E]." Where a FPE interface is required to be disabledthen use the FPE device disablement option.HMCPINTERFACE # MORE THAN ONE INTERFACE #DEVICE IN A VIGILON SYSTEMCAN BE SET UP TO OPERATE ASFIRE PROTECTION EQUIPMENT (FPE)SensorAlarmdeviceDuct mounted fire Dampers,Fixed fire fighting system,Sprinkler or water spray systemSmoke and Heat control system orHold open device for fire / smoke doorsFPEENABLED ORDISABLEDACTIONSETUPas FPEVigilon loopINTERFACE # Duct mounted fire Dampers,Fixed fire fighting system,Sprinkler or water spray systemSmoke and Heat control system orHold open device for fire / smoke doorsACTIONSETUPas FPE# - Can be a MV Interface unit S4-34411 or S4-34415FPEMORE THAN ONE INTERFACE #DEVICE IN A VIGILON SYSTEMCAN BE SET UP TO OPERATE ASFIRE PROTECTION EQUIPMENT (FPE)