Device digital I / O channelsMCP . . . O 6Repeat panel . . . O -Zonal mimic . . . O -Mimic panel . . . O -T-breaker . . . OLoop interface all possibleI - inputO - output1-channel 12-channel 23-channel 34-channel 45Interface unit (mains powered) all possibleI - inputO - output1-channel 12-channel 23-channel 34-channel 45-battery6-mainsS cubed OOOO1 - IR control2 - Tone3 - Power4 - VAD(Strobe)5Device digital I / O channelsThe legacy products below are for referenceS-Quad Dual Optical Heat Sensor Strobe O . . O 1, 2, 4, 5S-Quad Dual Optical Heat Sensor Sounder . OOO 1, 2, 4, 5S-Quad Dual Optical Heat Sensor Speech Strobe OOOO 1, 2, 4, 5S-Quad Dual Optical Heat Sensor CO SpeechStrobeOOOO 1, 2, 3, 4, 5Slave LED . . . O +LSounder . OO .3 - Low freq.2 - On/OffRepeat sounder . OO .Optical . . . O 1Optical heat . . . O 1,2Heat . . . O 4Slave Relay O . . O+RSingle channel interface unit I O . O 1,2,5Loop powered zone module I . . O 1,5Optical/Heat Sounder . OOO 1,2"The correct device type may not be displayed if the loop circuit has allocation faults.¨ Check that the device is of the correct type and is suitable for the area in which it isinstalled.¨ Check the digital status of all devices.¨ On successful allocation check that the total number of devices found equals thenumber installed. Also note there will be a loop voltage on the unconnected end of thecable.Commissioning instructions66 4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.Checking device STATUS