Vigilon Compact Voice Alarm Panel -(legacy product)The following procedures assume the Control panel is installed with cables terminated at thebackbox.¨ Open the Outer door of the enclosure using the door key supplied and then open theinner door.¨ Remove the protective cover fitted over the printed circuit boards located inside thebackbox.¨ Earth LeadEnsure the earth lead located at the top right of the backbox is connected to the spadeconnector on the inner door.¨ DAC ribbon cableConnect the 40-way ribbon cable from the DKC to the socket marked KEYBOARDon the left edge of the Master Control Board (MCB). Secure the ribbon cable to theside of the enclosure using the cable clamp provided.¨ ACC DAC ribbon cableRoute the 14-way ribbon cable from the backbox on to the inner door and connect itto the left unoccupied socket on the ACC DKC. Secure the ribbon cable to the innerdoor using the cable clamp provided.¨ Emergency microphone cableConnect the Emergency microphone cable to the socket P11 labelled 'microphone' onthe bottom edge of the ACC board. Secure the microphone lead to the 'P' clip on thebackbox.4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms. 45Vigilon 4/6 loops & Compact (VA) panels & network nodesVigilon Compact Voice Alarm Panel - (legacy product)Connect microphone cableto socket P11 labelled‘microphone’ on the ACCand secure cable to the P clip.Connect the 14-wayribbon to socketACC DKC.Secure 14-way ribbon to Inner doorusing cable clamps supplied.Connect the 40-way ribbon to the socket labelledKEYBOARD on MCB and secure cable to the sideof the enclosure.Fit the earth lead to the inner doorACCMCBACC DKCPSUMains terminal blockwith fuseP Clip formains cableREMOVAL OF COVEREXPOSES HIGH VOLTAGEWARNING