Commissioning instructions80 4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.34000 range of sensors STATES (legacy devices)STATES Definition ApplicationState 12 (LPC approved) Grade 1 Heat only No optical smoke detection. Can be used where airborne particles or smoke could occurbriefly or at specific times. Optical detection can be used in conjunction with timeblocks/slots to enable/disable sensor depending on application.State 13 (LPC approved) Grade 2 Heat onlyState 14 Grade 3 Heat onlyState 15 No detection This state can be used to provide total disablement on a timed or temporary basis.Heat sensor STATES (34000 range)STATES Definition ApplicationState 0 (LPC approved) (Default) Grade 2, rate of rise andfixed temperatureSuitable for general use in ambient temperatures up to 40oC. Provides detection toGrade 2 performance as defined in BS5445 : Part 5.State 1 (LPC approved) Grade 1, faster rate of temperaturerise as well as fixed temperatureApplicable for areas with normally very steady low ambient temperatures. A faster rateof rise can signal a fire below the normal set temperature at 58oC.State 2 Grade 1, limited rate of rise Applicable for normal ambient temperature where temperature variations are expectedup to 40oC but faster response than grade 2 is required e.g. hotel bedroom.State 5 High temperature with rate of rise Provides detection as specified by Range 1 BS5445:Part 8 .State 6 High temperature with no rate of rise Provides detection as specified by Range 1 BS5445:Part 8.State 15 No detection No detection. This is a total disablement of the sensor.