Message Action listThe messages displayed at the control panel, network node or loop repeat panels are given here in an alphanumerical order to provide guidance:¨ on a 'fault message'¨ the likely meaning of the message¨ along with suggestions on what initial actions may be taken to rectify the problem." Only the messages that are applicable will appear on the display of the control panel, network node or loop repeat panels. Additionally the display will identify the panelwhere the event was first detected.¨ The term device was previously referred to as outstation.Message associated with.. meaning.. ..possible actionA spurious FIRQ atcard xMCC / MCB(main control card/board)There is glitch on the MCC hardware that appears onthe backplane / MCB.Clear and ignore single occurrence.A spurious IRQ atcard xMCC / MCB(main control card/board)There is glitch on the MCC / MCB hardware. Clear and ignore single occurrence.A spurious NMI atcard xMCC / MCB(main control card/board)There is glitch on the MCC / MCB hardware. Clear and ignore single occurrence.A spurious SWI2 atcard xMCC / MCB(main control card/board)There is glitch on the MCC hardware. Clear and ignore single occurrence.A spurious SWI3at card xMCC / MCB(main control card/board)There is glitch on the MCC / MCB hardware. Clear and ignore single occurrence.Access fault atcard xAny Card Card cannot talk to the MCC / MCB local controller. Replace card if the fault keeps reoccurring.Could also be caused by excessive networkmessages. Investigate message passing.ACIA Failed atcard xNetwork Card orMCC / MCBCommunication chip failure or the FABs and SABs arecorrupt.Reset the card and replace if it fault keepsreoccurring.Alarms silenced MCC / MCB(main control card/board)Silence alarms button has been pressed. -4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms. 117Vigilon 4/6 loops & Compact (VA) panels & network nodesAppendix B - Message Action List