Cards and internal cables of the panelBatteryThe lithium battery s is disconnected on leaving the factory by means of an insulation disk overthe top connector. The insulation disk must be removed before powering up the system.Set the Rotary switch SW2This switch is set to the required position for the panel build on leaving thefactory. Before installing the Loop cards and Network card onto the Mastercontrol board MCB ensure the switch j SW2 is set to a required setting ifthe panel is to be installed in an existing system, see table on the next page.NVM hardware link P13The NVM can be enabled or disabled by setting the hardware link k on theMCB. If the NVM protect is hardware disabled then it is also possible tosoftware enable or disable the NVM using the [Protect] option under the[Setup] menu at the panel.Unprotect: Normally during commissioning the NVM is disabled(unprotected) and writing to NVM is allowed.Protect: Once the configuration is backed up to the NVM the hardware linkmust be in the enabled position to disallow writing to the NVM.Installing the CardsThe MCB can accommodate two Loop Cards. One Loop card l can befitted into the slot labelled CARD1 and the other Loop card n into the slotlabelled CARD2." A networkable system has a Network Card m fitted intothe slot CARD 2 on the MCB and additionally the Network Card canaccommodate the second Loop card.Earth LinkThe earth link lead o is supplied with the Network Card. This link leadmust be fitted to the spade connector on the top edge of MCB with the otherend to the spade connector on the Network Card.TerminalsThe terminal blocks p on the top edge of the MCB are used for wiringexternal circuits. The terminal block q on the top edge of the PSU is usedfor wiring the mains supply to the panel. The connector r located on thebottom edge of the PSU board is used to connect the battery supply.4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms. 35Vigilon 4/6 loops & Compact (VA) panels & network nodesVigilon Compact PanelWARNINGREMOVAL OF COVEREXPOSES HIGH VOLTAGEKEYBOARD INDICATORS AND DISPLAYL2-0V L2+ L1-0VPB1A PB1BP2PP2Network CardLoop Card 2P13P13 SW1RESETSW2MODENVM Protect - [Disabled]NVM Protect - [Enabled]BATT3PB15 PB6 PB9P2 CARD 1IC3KEYBOARDIC16POWERSUPPLYP12MA2 - FS2 250mAMA1 - FS1 250mAP1 CARD 2P16P13 SW1RESET24V B A0V TX1 RX1 0VPB8MA1+ MA1- MA2+ MA2-0V MIPNC C NOFIRMWARE BACKUPPB10 PB7L1 0V L2 0V24VFS3 200mATX2 RX2PB14L1 0V L2 0V NC C NO NC C NO NC C NOPB11Master ControlBoard (MCB)Power Supply Unit(PSU)P2P1N E LFS3 3.15A(T)Mains fuseP3DANGERFS61A TE543V FS4 - 1A TE524VP7BAT1FS1 - 3.15A TE5Bat 1Removeinsulation diskLNWarningRemoval ofcover exposeslive partsDANGERSW2MODELoop Card 1L1+BATT3Remove Sleeve