Commissioning instructions78 4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.Interface Unit STATESInterface Unit STATESSingle channel interface input STATESThese STATES also apply to loop powered single channel interface.STATE Definition ApplicationState 0 Default - allInputs enabledNormal useState 1 Input 1 disabled Selective disablement andenablement of interface input circuitsWhere an input circuit is used for firedetection application, the call pointson the circuits will NOT remainoperational on disablement of thecircuit.State 15 All inputsdisabledInterface input disablement4 - Channel Interface Unit STATESThese 4 - channel interface unit input STATES are applicable for both mains and loop poweredinterface units.STATE Definition ApplicationsState 0 Default - all Inputs enabled Normal useState 1 Input 1 disabled Selective disablement andenablement of interface inputcircuits" Where an inputcircuit is used for firedetection application, thecall points on the loopcircuit will remainoperational on disablementof the loop circuit.State 2 Input 2 disabledState 3 Inputs 1 and 2 disabledState 4 Input 3 disabledState 5 Inputs 1 and 3 disabledState 6 Inputs 2 and 3 disabledState 7 Inputs 1, 2 and 3 disabledState 8 Input 4 disabledState 9 Inputs 1 and 4 disabledState 10 Inputs 2 and 4 disabledState 11 Input 1, 2 and 4 disabledState 12 Inputs 3 and 4 disabledState 13 Inputs 1, 3 and 4 disabledState 14 Inputs 2, 3 and 4 disabledState 15 All inputs disabled interface input disablement