Chapter 6. Serial I/O, SNP & RTU ProtocolsGFK-2222AD April 2018 247Message (17): Report Device TypeFormat:Address Error CheckFunc 17QueryNormal ResponseAddress DeviceType 43Error CheckFunc 17 Slave RunLightDataByteCountFigure 62: RTU Report Device Type Message FormatQuery:The Report Device Type query is sent by the master to a slave in order to learn what type ofprogrammable control or another computer it is.▪ An Address of zero is not allowed as this cannot be a broadcast request.▪ The Function code is 17.Response:▪ The Byte Count field is one byte in length and is equal to 5.▪ The Device Type field is one byte in length and is equal to 43 (hexadecimal) for PACSystems▪ The Slave Run Light field is one byte in length. The Slave Run Light byte is equal to OFFH if the CPU isin RUN Mode. It is equal to 0 if the CPU is not in RUN Mode.▪ The Data field contains three bytes. For PACSystems CPUs, the first byte is the Minor Type, and theremaining bytes are zeroes. The following table lists minor types.Response Data(Minor Type) CPU Model8702 hex IC698CPE01004 hex IC698CPE02005 hex IC698CRE02006 hex IC698CPE03008 hex IC698CPE0400A hexIC695CPE302IC695CPE305IC695CPU3100C hex IC695NIU00110 hex IC695CPU32011 hex IC695CRU32012 hex IC695CPE302IC695CPE30518 hex IC695CPU31587 Does not apply to CPE330, which has no serial ports.