B.14 U: MonitorsMonitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.u U1: Operation Status MonitorsNo.(Addr.Hex) Name Description Analog OutputLevel UnitU1-01(40) Frequency Reference Monitors the frequency reference. Display units are determined by o1-03. 10 V: Max frequency 0.01 HzU1-02(41) Output Frequency Displays the output frequency. Display units are determined by o1-03. 10 V: Max frequency 0.01 HzU1-03(42) Output Current Displays the output current. 10 V: Drive ratedcurrent <1> <2>U1-04(43) Control Method 0: V/f Control No signal outputavailable –U1-06(45) Output Voltage Reference Displays the output voltage. 10 V: 200 Vrms <3> 0.1 VacU1-07(46) DC Bus Voltage Displays the DC bus voltage. 10 V: 400 V <3> 1 VdcU1-08(47) Output Power Displays the output power (this value is calculated internally). 10 V: Drive capacity(motor capacity) kW <4>U1-10(49) Input Terminal StatusDisplays the input terminal status.U1 - 10=00000000 Digital input 1(terminal S1 enabled)Digital input 2(terminal S2 enabled)Digital input 3(terminal S3 enabled)Digital input 4(terminal S4 enabled)Digital input 5(terminal S5 enabled)Digital input 6(terminal S6 enabled)Digital input 7(terminal S7 enabled)Digital input 8(terminal S8 enabled)11111111No signal outputavailable –U1-11(4A) Output Terminal StatusDisplays the output terminal status.U1 - 11=00000000 Multi-FunctionDigital Output(terminal MD-ME-MF)Digital Output(terminal M1-M2)Digital OutputMulti-FunctionMulti-FunctionNot UsedFault Relay(terminal MA-MC closedMA-MC open)11110(terminal M3-M4)No signal outputavailable –B.14 U: MonitorsYASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual 479B Parameter List