When this parameter is set to 0 (disabled) the drive will ignore the Run state of the drive when power is lost. When thisparameter is set to 1 (enabled), and the active Run source is from the digital operator, the drive will save the Run status duringpower-down.When power is restored, and the drive is still in operator mode, the previous Run status will be loaded and will apply the Runcommand.If the Run command was issued while the drive was running in LOCAL mode (triggered through the operator key) and powerwas cycled, the drive will not automatically run, as the default starting state is REMOTE operation.Note: The Run Status is saved on the terminal board and on the control card. If the Run Status does not match (e.g., if the terminal board wasreplaced), the Run Status is reset and the drive will not run on the next power-up.WARNING! Sudden Movement Hazard. If o2-20 is set to 1 and o2-06 is set to 0, the drive will continue running when the digital operator isremoved and may run automatically when power is cycled, resulting in death or serious injury. Clear all personnel from the drive, motor andmachine area before applying power. Secure covers, couplings, shaft keys and machine loads before applying power to the drive.No. Name Setting Range Defaulto2-20 Operator Run Save at Power Loss 0, 1 0Setting 0: DisabledSetting 1: Enabledu o3: Copy FunctionThese parameters control the Copy function of the digital operator. The Copy function stores parameter settings into thememory of the digital operator to facilitate the transfer of those settings to other drives that are the same model, capacity, andsame control mode setting. Refer to Copy Function Related Displays on page 325 for a description of errors and displays.n o3-01: Copy Function SelectionInstructs the drive to Read, Write, or Verify parameter settings.No. Name Setting Range Defaulto3-01 Copy Function Selection 0 to 3 0Setting 0: Copy Select (No Function)Setting 1: INV --> OP READCopies all parameters from the drive to the digital operator.Note: Set o3-02 to 1 to unlock copy protection.Setting 2: OP --> INV WRITECopies all parameters from the digital operator to the drive.Setting 3: OP<-->INV VERIFYCompares the parameters in the drive with the parameter settings saved on the digital operator for matches.n o3-02: Copy Allowed SelectionAllows and restricts the use of the Copy function.No. Name Setting Range Defaulto3-02 Copy Allowed Selection 0, 1 0Setting 0: DisabledSetting 1: Enabledu o4: Maintenance Monitor Settingsn o4-01: Cumulative Operation Time SettingSets the cumulative operation time of the drive. The user can also manually set this parameter to begin keeping track ofoperation time from some desired value. Total operation time can be viewed in monitor U4-01.Note: The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will alsobe displayed in monitor U4-01.No. Name Setting Range Defaulto4-01 Cumulative Operation Time Setting 0 to 9999 05.10 o: Operator Related Settings272 YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual