5.7 H: Terminal FunctionsH parameters assign functions to the external terminals.u H1: Multi-Function Digital Inputsn H1-01 to H1-08: Functions for Terminals S1 to S8These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in Table5.29.No. Parameter Name SettingRange DefaultH1-01 Multi-Function Digital Input Terminal S1 Function Selection 1 to 9F 40 (F) <1> : Forward Run Command (2-Wire sequence)H1-02 Multi-Function Digital Input Terminal S2 Function Selection 1 to 9F 41 (F) <1> : Reverse Run Command (2-Wire sequence)H1-03 Multi-Function Digital Input Terminal S3 Function Selection 0 to 9F 24: External FaultH1-04 Multi-Function Digital Input Terminal S4 Function Selection 0 to 9F 14: Fault ResetH1-05 Multi-Function Digital Input Terminal S5 Function Selection 0 to 9F 3 (0) <1> : Multi-Step Speed Reference 1H1-06 Multi-Function Digital Input Terminal S6 Function Selection 0 to 9F 4 (3) <1> : Multi-Step Speed Reference 2H1-07 Multi-Function Digital Input Terminal S7 Function Selection 0 to 9F 6 (4) <1> : Jog Reference SelectionH1-08 Multi-Function Digital Input Terminal S8 Function Selection 0 to 9F 8: (6) <1> : External Baseblock Command<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).Table 5.29 Multi-Function Digital Input Terminal SettingsSetting Function Page0 3-Wire Sequence 2061 LOCAL/REMOTE Selection 2062 External Reference 1/2 Selection 2073 Multi-Step Speed Reference 12074 Multi-Step Speed Reference 25 Multi-Step Speed Reference 36 Jog reference Selection 2077 Accel/Decel Time Selection 1 2078 Baseblock Command (N.O.) 2079 Baseblock Command (N.C.)A Accel/Decel Ramp Hold 207B Drive Overheat Alarm (oH2) 208C Analog Terminal Input Selection 208F Through Mode 20810 Up Command 20811 Down Command12 Forward Jog 20913 Reverse Jog14 Fault Reset 20915 Fast Stop (N.O.) 20917 Fast Stop (N.C.) 20918 Timer Function Input 21019 PID Disable 2101A Accel/Decel Time Selection 2 2101B Program Lockout 2101E Reference Sample Hold 21020 to 2F External Fault 21130 PID Integral Reset 21131 PID Integral Hold 211Setting Function Page32 Multi-Step Speed Reference 4 21134 PID Soft Starter Cancel 21135 PID Input Level Selection 21140 Forward Run Command (2-Wire sequence) 21241 Reverse Run Command (2-Wire sequence)42 Run Command (2-Wire sequence 2) 21243 FWD/REV Command (2-Wire sequence 2)47 Node Setup 21251 Disable Sequence Timers 21252 Cancel Active Sequence Timer 21260 DC Injection Braking Command 21261 External Speed Search Command 1 21262 External Speed Search Command 2 21263 Field Weakening 21365 KEB Ride-Thru 1 (N.C.) 21366 KEB Ride-Thru 1 (N.O.)67 Communications Test Mode 21368 High Slip Braking (HSB) 2136A Drive Enabled 21375 Up 2 Command 21376 Down 2 Command7A KEB Ride-Thru 2 (N.C.) 2147B KEB Ride-Thru 2 (N.O.)A8 Secondary PI Disable (N.O.) 214A9 Secondary PI Disable (N.C.) 214AA Secondary PI Inverse Operation 214AB Secondary PI Integral Reset 214AC Secondary PI Integral Hold 214AD Select Secondary PI Parameters 2155.7 H: Terminal FunctionsYASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual 2055 Parameter Details