u Rated Current Depending on Carrier FrequencyThe table below shows the drive output current depending on the carrier frequency settings.n Normal Duty Rating (ND)The 2 kHz values shown for ND in Table A.33 are equal to the drive rated current shown on the drive nameplate. Increasingthe carrier frequency above 2 kHz will reduce the ND rated output current of the drive as shown in Table A.33.Table A.31 Three-Phase 200 V Class Carrier Frequency and Current DeratingThree-Phase 200 V ClassDrive ModelRated Current [A]Normal Duty Rating (ND)2 kHz 8 kHz 15 kHz2A0004 3.5 3.2 2.562A0006 6 5 42A0008 8 6.9 5.52A0010 9.6 8 6.42A0012 12 11 8.82A0018 17.5 14 11.22A0021 21 17.5 142A0030 30 25 202A0040 40 33 26.42A0056 56 47 37.62A0069 69 60 482A0081 81 75 532A0110 110 85 602A0138 138 115 81Three-Phase 200 V ClassDrive ModelRated Current [A]Normal Duty Rating (ND)2 kHz 5 kHz 10 kHz2A0169 169 145 1162A0211 211 180 1442A0250 250 215 1722A0312 312 283 2262A0360 360 346 2772A0415 415 415 332Table A.32 Three-Phase 400 V Class Carrier Frequency and Current DeratingThree-Phase 400 V ClassDrive ModelRated Current [A]Normal Duty Rating (ND)2 kHz 8 kHz 15 kHz4A0002 2.1 1.8 1.14A0004 4.1 3.4 24A0005 5.4 4.8 2.94A0007 6.9 5.5 3.34A0009 8.8 7.2 4.34A0011 11.1 9.2 5.54A0018 17.5 14.8 8.94A0023 23 18 10.84A0031 31 24 14.4A.4 Drive Derating Data426 YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual