H7 ASD Operation Manual 89RR Speed Reference Setpoint #1 (frequency)Program ⇒ Frequency Setting Parameters ⇒ Speed ReferenceSetpoints ⇒ RRThis parameter is used to set the gain and bias of the RR input terminal whenthis terminal is used as the control input while operating in the Speed Controlmode.See F210 for further information on this setting.This parameter sets the RR Speed Reference Setpoint #1 (frequency) and isthe frequency that is associated with the setting of F210.Direct Access Number — F211Parameter Type — NumericalFactory Default — 0.0Changeable During Run — YesMinimum — 0.0Maximum — 100.0Units — HzRR Speed Reference Setpoint #2 (%)Program ⇒ Frequency Setting Parameters ⇒ Speed ReferenceSetpoints ⇒ RRThis parameter is used to set the gain and bias of the RR input terminal whenthis terminal is used as the control input while operating in the Speed Control orthe Torque Control mode.See F210 for further information on this setting.This parameter sets the RR input level that represents RR Reference Setpoint#2 (frequency) (torque or frequency). This value is entered as 0 – 100% of the0 – 10 VDC RR input signal range.Direct Access Number — F212Parameter Type — NumericalFactory Default — 100.0Changeable During Run — YesMinimum — 0.0Maximum — 100.0Units — %RR Speed Reference Setpoint #2 (frequency)Program ⇒ Frequency Setting Parameters ⇒ Speed ReferenceSetpoints ⇒ RRThis parameter is used to set the gain and bias of the RR input terminal whenthis terminal is used as the control input while operating in the Speed Controlmode.See F210 for further information on this setting.This parameter sets RR Speed Reference Setpoint #2 (frequency) and is thefrequency that is associated with the setting of F212.Direct Access Number — F213Parameter Type — NumericalFactory Default — 80.0Changeable During Run — YesMinimum — 0.0Maximum — 100.0Units — HzRR Torque Reference Setpoint #1 (%)Program ⇒ Torque Setting Parameters ⇒ Setpoints ⇒ RRThis parameter is used to set the gain and bias of the RR input terminal whenthis terminal is used as the control input while operating in the Torque Controlmode.This is accomplished by establishing an associated V/f output pattern for a givenRR input level and motor load.See F210 for further information on this setting.This parameter sets RR Torque Reference Setpoint #1 and is the output torquevalue that is associated with setting of F210. This value is entered as 0 – 250%of the rated torque.Direct Access Number — F214Parameter Type — NumericalFactory Default — 0.0Changeable During Run — YesMinimum — 0.0Maximum — 250.0Units — %F211 F214www . ElectricalPartManuals . com