88 H7 ASD Operation ManualRR Speed Reference Setpoint #1 (%)Program ⇒ Frequency Setting Parameters ⇒ Speed ReferenceSetpoints ⇒ RRThis parameter is used to set the gain and bias of the RR input terminal whenthis terminal is used as the control input while operating in the Speed Control orthe Torque Control mode.Perform the following setup to allow the system to receive control input at theRR terminal:• Program ⇒ Fundamental Parameters ⇒ Standard Mode Selection ⇒Command Mode ⇒ Use Control Terminal Strip.• Program ⇒ Fundamental Parameters ⇒ Standard Mode Selection ⇒Frequency Mode #1 ⇒ Use RR.• Provide a Run command (F or R).Gain and Bias SettingsWhen operating in the Speed Control mode, the settings that determine the gainand bias of the RR terminal are:• RR Speed Reference Setpoint #1 (frequency) (F211),• the RR input signal level that represents RR Speed Reference Setpoint #1(frequency): F210,• RR Speed Reference Setpoint #2 (frequency) (F213), and• the RR input signal level that represents RR Speed Reference Setpoint #2(frequency): F212.When operating in the Torque Control mode, the settings that determine thegain and bias of the RR terminal are:• Torque Reference Setpoint #1 (%) (F214),• the RR input signal level that represents the RR Torque ReferenceSetpoint #1 (%): F210,• Torque Reference Setpoint #2 (%) (F215), and• the RR input signal level that represents the RR Torque ReferenceSetpoint #2 (%): F212.Once set, as the RR input voltage changes, the output frequency or the outputtorque of the drive will vary in accordance with the above settings.This parameter sets the RR input level that represents RR Speed ReferenceSetpoint #1 (torque or frequency). This value is entered as 0 – 100% of the0 – 10 VDC RR input signal range.The input signal may be trimmed using F472 (Bias) and F473 (Gain).This parameter sets the RR input level that represents RR Speed ReferenceSetpoint #1 (torque or frequency). This value is entered as 0 – 100% of the RRinput signal range.Direct Access Number — F210Parameter Type — NumericalFactory Default — 0.0Changeable During Run — YesMinimum — 0.0Maximum — 100.0Units — %Frequency SettingsTorque SettingsF210 F210www . ElectricalPartManuals . com