104 H7 ASD Operation ManualJog Run FrequencyProgram ⇒ Frequency Setting Parameters ⇒ Jog SettingsThis parameter sets the output frequency of the drive during a Jog. Jogging isthe term used to describe turning the motor on for small increments of time andis used when precise positioning of motor-driven equipment is required.Enabling the Jog Window allows for the Manual Jog window to be among thescreens accessed during repeated MON/PRG entries. This screen must bedisplayed when Jogging using the EOI.The Jog function may be initiated from the EOI or remotely via the ControlTerminal Strip or using Communications (for further information on usingCommunications for Jogging, see the Communications manual).To perform a Jog, set this parameter (F260) to the desired Jog frequency.Select a Jog Stop method (F261).Jog Using the EOITo initiate a Jog from the EOI perform the following:1. Place a check in the Enable Jog Window box (Program ⇒ FrequencySetting Parameters ⇒ Jog Settings ⇒ Enable Jog Window).Note: The Jog Window must be displayed on the EOI to perform the Jogfunction using the EOI.2. Press MON/PRG to access the Jog Window.3. Using the Up/Down arrow keys of the EOI, select Reverse orForward.4. Place the system in the Local mode (Local/Remote LED is on).5. Press and hold the Run key for the desired Jog duration.Jog Using the Control Terminal StripTo initiate a Jog from the Control Terminal Strip perform the following:1. Assign a discrete input terminal to the Jog function (see Table 6 on pg.67).2. Assign a discrete input terminal to the F (Forward) function (andReverse if required) (see Table 6 on pg. 67).3. Provide a Forward and/or Reverse command from the ControlTerminal Strip.4. From the Jog Window, use the Up/Down arrow keys of the EOI toselect Reverse or Forward (Program ⇒ Frequency SettingParameters ⇒ Jog Settings ⇒ Enable Jog Window). Press MON/PRG to access the Jog Window.5. Place the system in the Remote mode (Local/Remote LED is off).6. Connect the assigned Jog terminal (from step 1) to CC for the desiredJog duration.Direct Access Number — F260Parameter Type — NumericalFactory Default — 0.00Changeable During Run — YesMinimum — 0.00Maximum — 20.00Units — HzF260 F260www . ElectricalPartManuals . com