H7 ASD Operation Manual 169RS485 Communications Time-Out ActionProgram ⇒ Communication Setting Parameters ⇒ CommunicationSettingsThis parameter plays a role in the setup of the communications network bydetermining the action to be taken in the event of a time-out (Time-OutAction).The communications network includes other ASDs and Host/Control computersthat monitor the status of the ASD(s), transfers commands, and loads ormodifies the parameter settings of the drive.Settings:No ActionAlarmTripDirect Access Number — F804Parameter Type — Selection ListFactory Default — TripChangeable During Run — YesCommunication IntervalProgram ⇒ Communication Setting Parameters ⇒ CommunicationSettingsThis parameter sets the Common Serial response delay time.Direct Access Number — F805Parameter Type — NumericalFactory Default — 0.00Changeable During Run — YesMinimum — 0.00Maximum — 2.00Units — SecondsTTL Master OutputProgram ⇒ Communication Setting Parameters ⇒ CommunicationSettingsIn a master/follower configuration, this setting determines the output parameterof the master ASD that will be used to control the applicable follower ASDs.Note: Select No Slave if F826 is configured as a Master Output controller.Otherwise, an EOI failure will result.Settings:No Slave (normal operation)Frequency ReferenceOutput Command FrequencyTorque CommandOutput Torque CommandDirect Access Number — F806Parameter Type — Selection ListFactory Default — No Slave (normaloperation)Changeable During Run — YesF804 F806www . ElectricalPartManuals . com