64 H7 ASD Operation ManualS5 Input Terminal AssignmentProgram ⇒ Terminal Selection Parameters ⇒ Input TerminalAssignment ⇒ S5This parameter selects the functionality of the S5 input terminal.Note: The S5 input terminal may be used without the ASD-Multicom optionboard.Without the ASD-Multicom option board the S5 terminal assignmentinformation will be stored in volatile memory. The terminal assignmentinformation will be lost if the system is powered down or reset.In addition, the input terminal must be specified as Normally Open orNormally Closed.This parameter sets the programmable S5 terminal to 1 of the 68 possiblefunctions that are listed in Table 6 on pg. 67.Direct Access Number — F119Parameter Type — Selection ListFactory Default — UnassignedChangeable During Run — NoS6 Input Terminal AssignmentProgram ⇒ Terminal Selection Parameters ⇒ Input TerminalAssignment ⇒ S6This parameter selects the functionality of the S6 input terminal.Note: The S6 input terminal may be used without the ASD-Multicom optionboard.Without the ASD-Multicom option board the S6 terminal assignmentinformation will be stored in volatile memory. The terminal assignmentinformation will be lost if the system is powered down or reset.In addition, the input terminal must be specified as Normally Open orNormally Closed.This parameter sets the programmable S6 terminal to 1 of the 68 possiblefunctions that are listed in Table 6 on pg. 67.Direct Access Number — F120Parameter Type — Selection ListFactory Default — UnassignedChangeable During Run — NoS7 Input Terminal AssignmentProgram ⇒ Terminal Selection Parameters ⇒ Input TerminalAssignment ⇒ S7This parameter selects the functionality of the S7 input terminal.Note: The S7 input terminal may be used without the ASD-Multicom optionboard.Without the ASD-Multicom option board the S7 terminal assignmentinformation will be stored in volatile memory. The terminal assignmentinformation will be lost if the system is powered down or reset.In addition, the input terminal must be specified as Normally Open orNormally Closed.This parameter sets the programmable S7 terminal to 1 of the 68 possiblefunctions that are listed in Table 6 on pg. 67.Direct Access Number — F121Parameter Type — Selection ListFactory Default — UnassignedChangeable During Run — NoF119 F121www . ElectricalPartManuals . com