154 H7 ASD Operation ManualPattern Run #14 Run-Time SettingProgram ⇒ Pattern Run Control Parameters ⇒ Preset Speeds ⇒ 14This parameter sets the run-time value for the #14 Preset Speed mode whenused as part of a Pattern Run.Direct Access Number — F598Parameter Type — NumericalFactory Default — 5Changeable During Run — NoMinimum — 1Maximum — 8000Units — SecondsPattern Run #15 Run-Time SettingProgram ⇒ Pattern Run Control Parameters ⇒ Preset Speeds ⇒ 15This parameter sets the run-time value for the #15 Preset Speed mode whenused as part of a Pattern Run.Direct Access Number — F599Parameter Type — NumericalFactory Default — 5Changeable During Run — NoMinimum — 1Maximum — 8000Units — SecondsElectronic Thermal Protection #1Program ⇒ Motor Parameters ⇒ Motor Set #1The Motor #1 Electronic Thermal Protection parameter specifies the motoroverload current level for motor set #1. This value is entered as either apercentage of the full load rating of the ASD or as the FLA of the motor.The unit of measurement for this parameter may be set to Amps or it may be setas a percentage of the ASD rating. The name-plated FLA of the motor may beentered directly when Amps is selected as the unit of measurement (see F701 tochange the display unit).Electronic Thermal Protection settings (#1 – #4) will be displayed in Amps ifthe EOI display units are set to V/A rather than %.Direct Access Number — F600Parameter Type — NumericalFactory Default — 100.0Changeable During Run — YesMinimum — 10.0Maximum — 100.0Units — %Overcurrent Stall LevelProgram ⇒ Protection Parameters ⇒ StallThis parameter specifies the output current level at which the output frequencyis reduced in an attempt to prevent a trip. The overcurrent level is entered as apercentage of the maximum rating of the drive.Direct Access Number — F601Parameter Type — NumericalFactory Default — (drive dependent)Changeable During Run — YesMinimum — 0.00Maximum — 200.0Units — %F598 F601www . ElectricalPartManuals . com