myNckAlarms|10000/NCKRegistering the alarm attribute fileThe alarm attribute file still has to be registered in order that the standard alarm texts arereplaced during the program runtime:1. You can copy a sample configuration file "oem_slaesvcconf.xml" from the followingdirectory: /siemens/sinumerik/hmi/template/cfg2. Save or create the file in the /oem/sinumerik/hmi/cfg or/user/sinumerik/hmi/cfg directory.3. Change the name to "slaesvcconf.xml".4. Open the file and in the tag enter the name of the alarm attribute file, e.g.NoteThe names of the tag can be freely selected. They must be unique in thesystem and must not clash with names used by Siemens.The tag name is reserved for Siemens.If you register additional alarm attribute files, i.e. you wish to include them in theconfiguration file, use the names , , etc.Restart SINUMERIK OperateThe files with the alarm texts and the attribute file still have to be converted into a binary formatin order that the alarm texts can be displayed during the program runtime. This data is onlyconverted during power up.To do this, restart SINUMERIK Operate. In the same directory where the .ts files or the alarmattribute file are located, files with the same name are created with the ".qm" and .hmi fileextension.The result of the conversion is written to the "alarmtext_conversion.log" or"oem_text_conversion.log" file. Errors that occur during the conversion, such as syntax errorsin a parameter file, are also written to the file.Configuring alarms13.2 Configuring alarm and message texts via alarm text filesSINUMERIK Operate (IM9)Commissioning Manual, 12/2017, 6FC5397-1DP40-6BA1273